Numerical Study of Bending Behavior for 66 kV Submarine Cables
Article information
Abstract
Submarine cables operate in complex marine environments and are repeatedly subjected to lateral loads from ocean currents, waves, and seabed irregularities. As these factors often create free spans that undergo substantial bending deformation, understanding the bending behavior of submarine cables is critical for ensuring their structural integrity. In this study, the bending behavior of a 66 kV submarine cable was investigated using a numerical approach, with particular emphasis on a novel modeling methodology that incorporates various conductor wire configurations. The numerical model was validated against experimentally obtained bending moment values through three-point bending tests, thereby ensuring an accurate representation of the structural response of the cable. As a result, the distribution of von Mises stress decreased by up to 27.3% as the cross-sectional area of the conductor wire increased under identical deflection. The single-conductor wire exhibited a bending moment approximately 132.3% higher than that of the 19-conductor wire. These findings indicate that assuming a conductor wire with a fully solid cross-section may lead to overestimation. This underscores the importance of determining the optimal number of conductor wires in 66 kV submarine cables, for which the proposed numerical modeling approach can be adopted.
1. Introduction
Offshore wind turbines face fewer restrictions related to land use compared to onshore wind turbines. Therefore, large-scale wind farms can be installed away from residential areas, avoiding issues such as noise pollution. Thus, the power generation capacity of offshore wind turbines has exhibited a continuous upward trend (Esteban et al., 2011). According to the Global Wind Energy Council (GWEC, 2022), an additional 21.2 GW of offshore wind capacity was installed worldwide by 2021, and the total installed capacity is projected to increase by 16.7%, reaching 316 GW by 2030. With an increase in the power generation capacity of offshore wind turbines, the performance requirements for submarine cables are becoming more stringent. In recent years, driven by the upscaling of offshore wind turbine capacities and advancements in floating offshore wind technology, typical 35 kV 3-core cross-linked polyethylene (XLPE) submarine cables are being increasingly replaced by 66 kV systems (Zhao et al., 2022), with major global manufacturers such as NKT, Nexans, Prysmian Group, and Hellenic Cables at the forefront of the design and production. Notably, the Prysmian Group and NKT together account for over 80% of the global 66 kV submarine cable market. This trend highlights the increasing technical sophistication and performance standards required for submarine cables (Zhao et al., 2022).
Submarine cables are exposed to complex marine environments for extended periods. During installation, 66 kV submarine cables are subjected to excessive tensile forces and bending moments (Yang et al., 2013, Poon et al., 2024), and during operation, they experience cyclic lateral loads induced by currents and waves, in addition to bending deformation and damage caused by seabed scour and seabed irregularities. Such bending behavior contributes significantly to the accumulation of fatigue damage within the cable components (Ménard & Cartraud, 2023), necessitating the evaluation of submarine cable bending performance (Huang et al., 2025). However, research on the bending characteristics of submarine cables remains limited because of their complex geometric architecture and nonlinear mechanical behavior arising from interlayer friction and slip effects (Ménard & Cartraud, 2023). In a study by Lu et al. (2017), the bending stiffness of submarine cables was quantitatively evaluated through analytical and numerical approaches, and curvature development was examined under varying interlayer contact and friction conditions. Similarly, the work of Cao et al. (2020) investigated the influence of several design parameters, including external pressure, friction coefficient, and helix angle of steel wires, on bending stiffness. However, these studies primarily focused on umbilical-type cables, in which all the structural layers, except the steel wires, are composed of rigid tubular components.
In 66 kV submarine cables, most structural components are arranged in a helical configuration to ensure flexibility. The helically arranged structure and geometry induce stick–slip interactions between adjacent layers, making the quantitative evaluation of bending stiffness particularly challenging (Skeie et al., 2012; Li et al., 2024). In a study by Ménard and Cartraud (2023), a three-dimensional finite element (3D FE) model was employed to investigate the bending behavior of submarine cables, applying the periodic beam homogenization theory to accurately represent the helical geometry. However, the numerical representation of the helically wound architecture and multilayered geometry in a 66 kV submarine cable incurs substantial computational cost and time. Therefore, some studies (Ménard & Cartraud, 2023; Fang et al., 2023) have employed beam-element–based numerical modeling to effectively reduce the computational cost and analysis time. However, such simplified approaches may not adequately capture the mechanical interactions between individual layers, raising concerns about the accuracy of bending behavior prediction (Lu et al., 2017). In addition, when performing bending analyses, the approach that assumes the conductor region to be a fully solid cross-section neglects inter-wire contact and friction effects, potentially leading to an overestimation of bending stiffness, which limits the ability to accurately reproduce the local stress distribution within the conductor (Nasution et al., 2014). Regarding the parameters that affect bending behavior, a three-point bending test (Maioli, 2015) was performed to evaluate the bending stiffness quantitatively, and the structural response under various bending radii was characterized in the form of hysteresis curves. Because experimental testing alone cannot sufficiently capture the influence of individual parameters on bending behavior, numerical analyses were conducted to assess the effects of different conductor wire counts.
Considering these challenges, the present study numerically investigated the bending behavior of a 66 kV submarine cable to optimize the number of conductor wires. In addition, the numerical modeling methodology was validated against the experimentally obtained bending moment values through three-point bending tests. Unlike previous studies, this study employed a distinct modeling methodology by constructing various conductor wire configurations to represent the structural behavior of the cable more accurately. The numerical results were compared with experimental values, and based on these findings, the optimal number of conductor wires for the 66 kV submarine cable was determined using the proposed numerical modeling approach.
2. Theory and Background
The theoretical evaluation of the bending stiffness of submarine cables varies depending on the interlayer contact conditions and occurrence of slip between components. As illustrated in Fig. 1, bending behavior is strongly dependent on the helix angle and mean radius of the helical layer, leading to rotational deformation (θ) of the wire (Chang & Chen, 2019). In general, submarine cable slip conditions can be categorized into two types: no slip and complete slip. In a study by Qin et al. (2024), a predictive model for bending stiffness was proposed, considering the effects of various helix angles and incorporating slip conditions, as expressed by the following equations:
Here, E denotes the elastic modulus; d is the diameter; R represents the mean radius of the helical layer; and α is the helix angle. The subscript o refers to the bending stiffness of the cylindrical layer, and i indicates the parameters corresponding to the i-th helical layer.
In the analytical model of the submarine cable investigated in this study, all components except the yarn are arranged in a helical configuration, making theoretical approaches inherently challenging. Furthermore, each component exhibits distinct material and structural properties such as different helix angles and elastic moduli. Therefore, this study aimed to establish a reliable analytical model based on the experimental data obtained from in situ measurements.
3. Bending Test
A bending test was conducted to evaluate the bending behavior of the submarine cable under conditions simulating cable laying and operation. The objective was to measure the bending stiffness and curvature of a cable subjected to bending loads. The 66 kV submarine cable used for the bending test consisted of three cores, each comprising a conductor, an insulation layer, various polyethylene (PE) layers, and a sheath arranged with a uniform pitch. Armor wires and yarns were placed on the outer surface of the cable. As shown in Fig. 2, bending stiffness was measured using a three-point bending test apparatus. In the three-point bending test, the cable specimen was fixed at both ends and displacement was applied at the center. Before testing, the origin of the bending-stiffness apparatus was adjusted based on the outer diameter of the submarine cable. The cable specimen was then inserted into the apparatus, and a vertical displacement of approximately ±1 m was applied at the center of the specimen. The specifications and configuration of the bending stiffness measurement device are summarized in Table 1. The total length of the cable specimen (L1) was 5 m, and the distance between the two supports (L2) was 3 m. Both supporting ends were designed to allow rotation, ensuring that the vertical reaction forces can be accurately measured without introducing additional constraints. Because of the nature of the bending test, a sufficiently long support span must be ensured; therefore, it was set to more than 15 times the outer diameter of the cable. Displacement loading was applied 1 m upward and downward from the center of the specimen, and the results are presented in the form of a hysteresis curve in Fig. 3. According to the bending test results, when a vertical displacement of 104.27 mm was applied, a corresponding bending force of 480.53 N was observed, indicating that the static numerical analyses in Eq. (3) correspond to a cantilever-beam formulation suitable for the test conditions. The bending moment at the midspan location
The bending stiffness was obtained from the maximum and minimum points of the bending cycle and calculated using Eq. (4). In general, the ratio between the maximum and minimum bending stiffnesses of a submarine cable can vary by up to one order of magnitude (Maioli, 2015). In this study, the maximum and minimum bending stiffness values were determined to be 2.86 kN·m2 and 0.38 kN·m2, respectively, indicating a difference of approximately 7.5 times between the two. This variation is attributed to the anisotropic bending behavior of the cable caused by its helical and composite structural configuration.
where EI is the bending stiffness; F is the applied load; L2 is the distance between the supports; and d is the vertical displacement at mid-spin.
4. Numerical Analysis
4.1 Numerical Modeling, Properties and Boundary Conditions
Geometric modeling of the submarine cable was performed using Design Modeler, provided by the commercial finite element analysis software Ansys 2023 R1, and structural analysis was conducted using Ansys Mechanical. The structural analysis was based on the bending moment measured from the three-point bending test. The reliability of the model was assessed by comparing the simulation results with experimental data to evaluate the error rate. As shown in Fig. 4, the constructed submarine cable model included the individual components corresponding to each layer. The total length of the analytical model was 1.55 m, and its diameter was 0.182 m. In the 66 kV submarine cable, all parts except the yarn were helically structured. The helix angle and pitch length of the steel wires were 19.48° and 1473 mm, respectively. The remaining three cores, excluding the steel wires, were configured with a helix angle of 6.62° and pitch length of 2271 mm. The mesh was generated using the sweep method (Lee, 2020) and applied to all the surfaces, resulting in a mesh composed entirely of hexahedral elements. The total number of elements and nodes used in the analysis were 225,900 and 1,186,377, respectively.
The material properties of the 66 kV submarine cable were determined based on experimental measurements (Im et al., 2024). The cable consisted of nonmetallic components that included the conductor screen, insulation, insulation screen, corrosion, and shaped filler, as well as metallic components, such as conductors, sheaths, and steel wires. The material properties are listed in Table 2.
The complex configuration of the 66 kV submarine cable generated numerous contact interfaces between the components, making it essential to define the contact and target surfaces at each interface, to appropriately assign contact types. In this analysis, both bonded and no-separation contact conditions were applied (Fig. 5). The bonded formulation was used when the entire interface remained in continuous contact without sliding, enforcing zero relative displacement in both normal and tangential directions. In contrast, the no-separation formulation suppresses the opening in the normal direction while permitting tangential sliding, whereby it is constrained against separation but free to slide in-plane. Additionally, for the steel wires, which were expected to exhibit the highest stress concentration, frictional contact was defined at the interface with the yarn, and a coefficient of friction of 0.2, corresponding to polyethylene (PE) and steel, was applied (Tuckart et al., 2014).
For the boundary conditions, the displacement and constraint conditions were applied at the two cable ends based on the experimental test settings. As shown in Fig. 6, a vertical displacement of −53.86 mm was applied at one end, corresponding to a bending moment of 720.79 N·m. In addition, the boundary conditions were established with reference to the methodology proposed by Li et al. (2024), who conducted similar bending tests and numerical analyses on submarine cables. In their approach, all translational and rotational degrees of freedom (Dx, Dy, Dz, Rx, Ry, Rz) were constrained to the opposite end of the cable specimen.
4.2 Numerical Results
In actual 66 kV submarine cables, each component has distinct characteristics, such as cross-sectional area, helix angle, and elastic modulus, making it impractical to include all components in a full-scale finite element model. As the number of wires within the conductor is approximately 60 per core, applying this configuration directly to the model would result in an excessive number of mesh elements and severe interference effects, rendering the analysis computationally infeasible. Therefore, the components should be simplified and the reliability of the analysis should be validated by evaluating the error between the simulation results and experimental data. In particular, assuming a fully filled cross-section for the conductor wires can lead to bending stiffness overestimation because of the d4 dependence in Eq. (1). Accordingly, we conducted a sensitivity analysis on the number of conductor wires, as summarized in Table 3. The internal arrangement of the conductor wires was based on a reference layout (Wikipedia, 2018). Through this analysis, the error between the numerical and experimental results was assessed, to determine the most suitable conductor-wire configuration for the analytical model.
4.2.1 Displacement in bending load
A numerical analysis was performed to evaluate the bending performance of the 66 kV submarine cable according to the number of wires in the conductor. The overall displacement distribution generated in the cable under the bending load is shown in Fig. 7. The total displacement increased linearly along the axial direction of the cable, indicating a uniform deformation pattern. The maximum displacement occurred in the outermost steel wire and ranged from 0.0544 to 0.0549 mm. Compared with the applied displacement load of 0.05386 mm, the deviation was less than 2%, confirming that an additional displacement was induced by the slip between the elements and rotational deformation of the structure.
4.2.2 Equivalent stress in bending load
In the bending analysis, von Mises stress was evaluated to determine whether yielding occurred under the applied bending load. Structural safety was ensured when the maximum von Mises stress did not exceed the yield strength of the material. The distribution of von Mises stress according to the number of wires in the conductor is shown in Fig. 8. The analysis results indicate that the maximum von Mises stress primarily occurred in the steel wires located in the upper region of the cable. This is attributed to the higher Young’s modulus of the steel wires, which are designed to provide mechanical protection against external loads. Among the analyzed cases, the highest stress value was observed in the single-conductor wire model (Fig. 8(a)), where the maximum von Mises stress reached approximately 182.65 MPa, whereas the lowest stress was observed in the 21-conductor wire model (Fig. 8(d)), with a maximum value of approximately 132.76 MPa. These results demonstrate that the maximum von Mises stress decreases by up to 27.3% as the number of conductor wires increases. This reduction is attributed to the increased bending stiffness resulting from the larger total cross-sectional area of the conductor, which reduces the stress induced by the same deflection. Regarding structural safety, the maximum von Mises stress in all cases was approximately 50% lower than the yield strength of the structural steel (355 MPa), confirming that the structural integrity of the submarine cable was sufficiently maintained under the applied bending load.
4.2.3 Comparison with experimental results
In this study, the vertical reaction force and bending moment were obtained from numerical bending analysis, and the overall results are summarized in Table 4 for comparison with the experimental data. The bending analysis results according to the number of wires within the conductor of the 66 kV submarine cable generally exhibited a trend proportional to the bending stiffness parameter (d4 × n), indicating that the bending moment decreases as the diameter of the individual conductor wires decreases. A maximum bending moment of 1683.2 N·m was observed in the single conductor wire case, which exhibited an error of approximately 134% compared to the experimental value. In contrast, the minimum bending moment of 704.10 N·m occurred in the 21-conductor wire case, with a corresponding error rate of 2.31%. The lowest error was observed in the 19-conductor wire case, with bending moment calculated as approximately 721.98 N·m, resulting in a highly accurate prediction with an error rate of only 0.17%. Fig. 9 presents a bar graph summarizing all the bending analysis results, highlighting the deviation from the experimental values. The optimal number of conductor wires for the 66 kV submarine cable was identified using the proposed numerical modeling approach.
5. Conclusion
In this study, the bending behavior of a 66 kV submarine cable was investigated using a numerical approach, with particular emphasis on a novel modeling methodology that incorporates various conductor wire configurations. The numerical model was validated against experimentally obtained bending moment values through three-point bending tests, thereby ensuring an accurate representation of the structural response of the cable. In the numerical analyses, the total displacement of the submarine cable increased linearly along the axial direction depending on the number of wires within the conductor. The maximum displacement occurred at the outermost steel wire and ranged from 0.0544 to 0.0549 mm. In the von Mises stress distribution, the maximum stress was also concentrated in the steel wire, which exhibited the highest Young’s modulus among the cable components. The bending moment analysis revealed that the single-conductor wire model exhibited the highest bending moment of 1683.2 N·m, showing the largest deviation–approximately 134%–when compared with the experimental results. In contrast, the 19-conductor wire model yielded a bending moment of 721.98 N·m, which was in excellent agreement with the measured value, showing only 0.17% deviation. Overall, the bending moment results exhibited a trend proportional to the bending stiffness parameter (d4 × n), demonstrating that a smaller wire diameter within the conductor leads to a reduction in bending moment. Furthermore, the single-conductor wire model produced a bending moment approximately 132.3% higher than that of the 19-conductor wire model, indicating that excessive stiffness may result in overestimation of bending responses in fully solid conductor configurations.
Notes
SungWoong Choi serves on the journal publication committee of the Journal of Ocean Engineering and Technology and had no role in the decision to publish this article. No potential conflicts of interest relevant to this article were reported.
This work was supported by the Korea Institute of Energy Technology Evaluation and Planning (KETEP) grant funded by the Korean government (MOTIE) (20213000000020, Development of core equipment and evaluation technology for construction of subsea power grids for offshore wind farms).